Basic Heating & Cooling Load

Select the variable you wish to calculate, input the known parameters, and the fluid properties will auto-solve dynamically.

Air Side Calculation

kW
L/s
°C
°C
Fluid properties dynamically calculated...

Water Side Calculation

kW
L/s
°C
°C
Fluid properties dynamically calculated...

Detailed Calculation Methodology

The standard thermodynamic equations for Sensible Air Load and Water Load rely on the mass flow rate, specific heat capacity (Cp), and the absolute temperature difference between entering and leaving conditions. To maintain strict precision, this tool calculates fluid density dynamically based on the average operating temperature.

Air Side Equations

Qair = V1000 × ρair × Cp(air) × [ Tentering - Tleaving ]

Water Side Equations

Qwater = V1000 × ρwater × Cp(water) × [ Tentering - Tleaving ]

Cooling Load Check Figures

Occupancy (air conditioned area) Cooling Load (W/m²)
Apartments, residence (un-insulated, poorly sealed and west facing)200
Apartments, residence (insulated, well-sealed and not facing west)120
Auditorium280
Banks175
Hairdresser215
Beauty Shop260
Cafeteria350
Classroom95
Clinic190
Clothing Store165
Computer Room480
Conference Room275
Department Store: Basement125
Department Store: Main Floor150
Department Store: Upper Floors125
Factory – Light Manufacture275
Factory – Heavy Manufacture490
Food Stores160
Hotel & Motel Rooms120
Laboratory130
Library150
Mall135
Medical Offices185
Milk Bars, Fast Food270
Office – General (Perimeter)170
Office – General (Interior)100
Office – Private180
Post Office180
Restaurants330
Shoe Store185
Supermarket160
Theatre280

Reference : AIRAH Technical Handbook